Rockwell Automation Publication 1788-UM059A-EN-P - August 2014
15
Install the Linking Device
Chapter 2
Set the Linking Device IP Address by Using RSLinx Software
To use RSLinx software to set the IP address of the linking device, follow these
steps.
1. Connect to the linking device using a USB cable.
2. From the Communications menu, choose RSWho.
3. Navigate to the USB port.
4. Right-click the linking device and choose Module Configuration.
5. Click the Port Configuration tab.
6. For Network Configuration Type, click Static to permanently assign this
configuration to the port.
7. Type the desired information in the appropriate boxes.