Chapter 3
Configure the Linking Device
13. If an RSNetWorx for DeviceNet configuration file (filename *.dnt) already
exists for the linking device, enter or browse to the appropriate filename.
Doing so lets RSNetWorx for DeviceNet software launch directly from the
Studio 5000 environment.
14. Click OK.
You can now use the linking device as both a bridge and a scanner.
15. Write a user program to use the linking device on the network.
16. To view information specific to the Logix Designer application tags that
pertain to the linking device, do the following.
a. In the left pane, click Controller Tags.
In the right pane, you see the 1788-EN2DNR linking device controller
tags.
b. Click the + to the left of the tag name to expand it.
c. Review data in the boxes that appear for each tag, as described in the
section entitled
Assembly Objects and Connections on page 31
TIP
Consult Rockwell Automation Technical Support or your Rockwell
Automation representative for assistance in writing the program.