Install the Linking Device

Chapter 2

The IP address can be set with the web page only if the linking device already has
a valid IP address. One way that you can do this is by using the rotary switch to
force the linking device to use the IP address from the switches after you cycle
power. Follow these steps to configure the IP address with the web page.

1. Browse to the linking device by entering the IP address set by the switches

in your web browser’s address bar and press Enter.

2. In the left pane, click Network Configuration.

The Enter Network Password dialog box appears.

3. In the User Name box, type Administrator.
4. In the password box, type the default password, which is the serial number

of the linking device in hexadecimal format, upper case.

The serial number can be found on the 1788-EN2DNR web page.

5. Click OK.

The Network Configuration dialog box appears.

IMPORTANT

Because the rotary switches setting overrides other IP address configurations,
be sure to set the rotary switches to the 0 position before continuing.