Ring statistics, Crash display, Heap statistics – Rockwell Automation 1788-EN2DNR EtherNet/IP to DeviceNet Linking Device User Manual User Manual

Page 45: Crash display heap statistics, Diagnostic web pages— miscellaneous

Advertising
background image

Rockwell Automation Publication 1788-UM059A-EN-P - August 2014

45

Diagnostic Web Pages

Chapter 6

Media Counters Port 1/Port 2

Ring Statistics

This section contains information about the topology of the network, and
specific ring information.

Diagnostic Web Pages—
Miscellaneous

The following sections explain the miscellaneous sections of the diagnostic web
pages.

Crash Display

This is the hexadecimal dump of the current fatal event log, that is stored in the
linking device. If no crash has ever occurred, the contents are all zero.

Heap Statistics

This information is only for support issues.

Field

Description

Alignment Errors

A frame containing bits that do not total an integral multiple of eight.

FCS Errors

A frame containing eight bits, at least one of which has been corrupted.

Single Collisions

The number of outgoing packets that encountered only one collision during
transmission.

Multiple Collisions

The number of outgoing packets that encountered 2...15 collisions during
transmission.

Excessive Collisions

The number of frames that experience 16 consecutive collisions.

MAC Transmit Errors

Frames for which transmission fails due to an internal MAC sublayer transmit error.

Frame Too Long

The number of incoming packets that exceed the maximum Ethernet packet size.

MAC Receive Errors

Frames for which reception on the Ethernet interface failed due to an internal MAC
sublayer receive error.