Diagnostic Web Pages

Chapter 6

80

Module is in IDLE mode

Put controller in RUN mode. Enable RUN bit
in module command register.

81

Module is in FAULT mode

Check Module Command Register for fault
bit set.

82

Error detected in sequence of fragmented I/O
messages from device

Check scan list table entry for slave device to
make sure that input and output data
lengths are correct. Check slave device
configuration.

83

Slave device is returning error responses when
module attempts to communicate with it

Check accuracy of scan list table entry. Check
slave device configuration. Slave device can
be in another master’s scan list. Reboot slave
device.

84

Module is initializing the DeviceNet network

None. This code clears itself once module
attempts to initialize all slave devices on the
network.

85

Data size was incorrect for this device at
runtime

Slave device is transmitting incorrect length
data. Try replacing the device.

86

Device is producing zero length data (idle
state) while module is in Run mode

Check device configuration and slave node
status.

87

The primary owner has not allocated the slave

Put the primary owner on line.

88

The connection choices (such as polled or
strobed) between the primary connection and
the shared input only connection do not
match

Reconfigure the shared input only
connection's choices to be the same as, or a
subset of, the primary connection's
choice(s).

89

Slave device initialization using Auto Device
Replacement parameters failed

Put the slave device into configurable mode.
Check the slave's EDS file, if the slave is
configured offline.
Check to see if the slave device has been
replaced with an incompatible device.

90

User has disabled communication port

Check Module Command Register for
DISABLE bit set.

91

Bus-off condition detected on comm port.
Module is detecting communication errors

Check DeviceNet connections and physical
media integrity. Check system for failed
slave devices or other possible sources of
network interference.

92

No network power detected on
communication port

Provide network power. Make sure that
module drop cable is providing network
power to module comm port.

95

Application nonvolatile memory update in
progress

Do nothing. Do not disconnect the module
while application nonvolatile memory
update is in progress. You lose any existing
data in the module’s memory.

96

COMM port in Test mode

Do nothing.

97

Module operation halted by user command

Check Module Command Register for HALT
bit set.

98

General firmware error

Replace module.

99

System failure

Replace module.