Rockwell Automation Publication 1788-UM059A-EN-P - August 2014

Chapter 3

Configure the Linking Device

10. Click Close.

11. Restart RSNetWorx for DeviceNet software and go online.

IMPORTANT

The linking device automatically restarts the DeviceNet network if a
new node address is entered. If the communication rate is changed,
you must cycle power to the linking device before the new
communication rate takes effect.

Note: Data rate changes can cause bus-off errors. Do not change the
data rate during live network performance.

TIP

If you are using the linking device as a network gateway, you need to
restart RSNetWorx for DeviceNet software before continuing.