22
Rockwell Automation Publication 1788-UM059A-EN-P - August 2014
Chapter 3
Configure the Linking Device
10. Click Close.
11. Restart RSNetWorx for DeviceNet software and go online.
IMPORTANT
The linking device automatically restarts the DeviceNet network if a
new node address is entered. If the communication rate is changed,
you must cycle power to the linking device before the new
communication rate takes effect.
Note: Data rate changes can cause bus-off errors. Do not change the
data rate during live network performance.
TIP
If you are using the linking device as a network gateway, you need to
restart RSNetWorx for DeviceNet software before continuing.