Set the linking device ip address – Rockwell Automation 1788-EN2DNR EtherNet/IP to DeviceNet Linking Device User Manual User Manual
Page 12
![background image](/manuals/579864/12/background.png)
12
Rockwell Automation Publication 1788-UM059A-EN-P - August 2014
Chapter 2
Install the Linking Device
Set the DeviceNet Node Address and Data Rate by Using RSNetWorx
for DeviceNet Software
Set the DeviceNet Node Address and Data Rate on page 20
for information
about using RSNetWorx software to set node address and data rate.
Set the Linking Device
IP Address
Four methods can be used to set the linking device IP address:
• Use the IP address rotary switches on the side of the linking device
• Use the DHCP protocol
• Use RSLinx Software
• Use the web pages of the linking device
Set the Linking Device IP Address by Using the Rotary Switches
The rotary switches are on the right side of the linking device.
Set the IP address according to the table below.
1
250 kbps
2
500 kbps
Other value
Data rate selected via RSNetWorx
software
Switch
Data Rate
Switch
IP Address
000
Administrative mode
The linking device uses the IP address that was used last startup
The web pages are available
001 - 254
192.168.1.XYZ where XYZ is the value of the three switches
888
Reset the linking device to initial out-of-box settings
Other value
The linking device starts in operating mode, using the latest configured IP
address
x100
x10
x1