Rockwell Automation Publication 1788-UM059A-EN-P - August 2014

23

Configure the Linking Device

Chapter 3

Enable/Disable Autobaud

Autobaud is disabled by default. You can turn it on or off by following the
procedure below.

1. In RSNetWorx for DeviceNet software, click the linking device icon.
2. From the Device pull-down menu, choose Class Instance.
3. If a warning dialog box appears, click Yes.

The Class Instance Editor dialog box appears.

4. From the Description pull-down menu, choose Set Single Attribute.

5. Choose the appropriate options in the Class Instance Editor dialog box.

In This Box

Choose

Object Address
Class
Instance
Attribute

3
1
64h

Data Sent to Device

00 to enable Autobaud
01 to disable Autobaud

Transmit Data Size

Byte

IMPORTANT

Make sure the Values in Decimal checkbox is cleared.