Chapter
Call Routines 0–68

12

12 -46

This call is active until you re-execute it with different input parameters.

Input and Output Arguments

This call has ten input arguments and one output argument.

Argument

Description

Page

input 1

type of DH-485 READ

12 -46

input 2

node address of the DH-485 remote device (0 through 31)

12 -46

input 3

file number on the DH-485 remote device (0 through 255)

12 -46

input 4

file type to be read from the remote device

12 -47

input 5

starting word offset within the file on the remote device (0
through 32766)

12 -47

input 6

number of words to be transferred

12 -47

input 7

the message time-out value

12 -47

input 8

the selection of the destination file and/or string

12 -48

input 9

always 1

12 -48

input 10

the string number

12 -48

output 1

call status

12 -48

To disable this call, you must PUSH a 0 into the first input parameter.
All other parameters are ignored, but you must still PUSH them.

Input Argument One
The first input argument is the type of DH-485 READ command issued:

0 = disable the previously executed CALL 49
1 = common interface file (CIF) read
2 = SLC typed read

Input Argument Two
The second input argument is the node address of the DH-485 remote
device (0 through 31). If the number is not within this range, the status
equals 2 and the read message does not occur.

Input Argument Three
The third input argument is the file number on the DH-485 remote device
(0 through 255). If the number is not within this range, the status equals 2
and the read message does not occur. The parameter is ignored if you
choose the Common Interface File (CIF) in the first parameter. The CIF is
always file 9.