Rockwell Automation 1771-DB BASIC MODULE User Manual

Page 328

Advertising
background image

Chapter
Call Routines 69–127

13

13 -70

Input Argument Three
The third input argument is the file number to be written to on the PLC
remote device (0 through 255). If the number is not within this range, the
status equals 2 and the write message does not occur. If you choose the
common interface file in the first parameter this input is ignored, but you
must still PUSH it.

Input Argument Four
The fourth input argument is the destination file type on the remote device.
This number is ignored if you choose the common interface file in the first
parameter (assumes integer file). If file type code is not one shown in the
table the status equals 2 and write message does not take place.

File type

File type code

Words/Element
(1 word = 16 bits)

integer file

ASC(N)

1 word/element

status file

ASC(S)

1 word/element

counter file

ASC(C)

3 words/element

timer file

ASC(T)

3 words/element

bit file

ASC(B)

1 word/element

control file

ASC(R)

3 words/element

input file

ASC(I)

1 word/element

output file

ASC(O)

1 word/element

Input Argument Five
The fifth input argument is the starting word offset within the file on the
PLC-2 remote device (0 through 32766). For PLC-3 integer, binary, or
status files, the value is 0–9999 (decimal). For PLC-3 I/O files, the value
is 0–4095 (decimal). For PLC-3 timer or counter files the value is 0.
If the number is not within this range, the status equals 2 and the transfer
does not occur.

Input Argument Six
The sixth input argument is the number of elements to be transferred.
If the number is not within the range shown below, the status equals 2 and
the transfer does not occur.

File type code

Valid element length range

ASC(N)

1 to 63

ASC(S)

1 to 63

ASC(C)

1 to 21

ASC(T)

1 to 21

ASC(B)

1 to 63

ASC(R)

1 to 21

ASC(I)

1 to 63

ASC(O)

1 to 63

common interface file

1 to 63