Specifications, A-11, A –11 – Rockwell Automation 1771-DB BASIC MODULE User Manual
Page 343: Environmental conditions, Backplane power consumption, Port driver and receiver, Module location, Keying

Product Overview
Appendix A
A –11
Environmental Conditions
Condition
Range
Operating temperature
0
°
C to 60
°
C (32
°
F to 140
°
F)
Storage temperature
–40
°
C to 85
°
C (–40
°
F to 185
°
F)
Relative humidity
5% to 95% (non–condensing)
Backplane Power Consumption
Operating voltage
Current requirement
5V dc
.75 Amps
Important: The BASIC module receives its power from the 1771-I/O
backplane. The power consumption of the BASIC module must be taken
into consideration when planning your PLC system. Refer to the
documentation supplied with your PLC processor or 1771-I/O equipment
for additional information on power supplies and current requirements.
Port Driver and Receiver
Drive output
Receiver sensitivity
+3.6 V minimum
200 mV minimum
Module Location
One 1771 I/O chassis module slot. See Chapter 1 for further details.
Keying
Top backplane connector:
between 8 and 10
between 32 and 34
See Chapter 1 for further details.
Specifications
Chapter
Keying Clips
.
Upper
Connector
Chapter