Chapter
Programming Block-Transfers

5

5 -3

Input Image Table

Input Image Table Bit

Description

Used with CALL

00

Do not use–Reserved

01

BTW Req

3 and 6

02

BTR Req

2 and 7

03

Do not use–Reserved

04

DF1 Status BTR Req

123

05–07

Do not use–Reserved

10

PRT1 BTW Req

33 (PRT1)

11

PRT1 BTW Ack

34 (PRT1)

12

PRT2 BTR Req/ DF1 BTR Ack

33 (PRT2), 122

13

PRT2/DF1 BTW Ack

34 (PRT2), 123

14

DH-485 READ Ack

49

15

DH-485 WRITE Ack

50

16

DH-485 Status BTR Req

50

17

Unsolicited DH-485/DF1 WRITE

118

See Chapter 12 and 13 for information on these calls.

Important: When the BASIC module is in 16-point mode you must
perform all block-transfers synchronously with a PLC-5 family processor.
Asynchronous block transfers do not work with this configuration and
cause the backplane circuit within the module to lock up. The BASIC
module ships with JW5 configured for 8-point mode (Series A
compatible). Unless you are using calls 32, 33, 34, 49, 50, 118, 122, or
123 (see Chapters 12 and 13) you should be in 8 point mode.

Important: You cannot use 2-slot chassis addressing if JW5 is set for 16
point mode. See page 1 -10 for information regarding the backplane
configuration and addressing.