Input image table – Rockwell Automation 1771-DB BASIC MODULE User Manual
Page 77

Chapter
Programming Block-Transfers
5
5 -3
Input Image Table
Input Image Table Bit
Description
Used with CALL
①
00
Do not use–Reserved
–
01
BTW Req
3 and 6
02
BTR Req
2 and 7
03
Do not use–Reserved
–
04
DF1 Status BTR Req
123
05–07
Do not use–Reserved
–
10
PRT1 BTW Req
33 (PRT1)
11
PRT1 BTW Ack
34 (PRT1)
12
PRT2 BTR Req/ DF1 BTR Ack
33 (PRT2), 122
13
PRT2/DF1 BTW Ack
34 (PRT2), 123
14
DH-485 READ Ack
49
15
DH-485 WRITE Ack
50
16
DH-485 Status BTR Req
50
17
Unsolicited DH-485/DF1 WRITE
118
①
See Chapter 12 and 13 for information on these calls.
Important: When the BASIC module is in 16-point mode you must
perform all block-transfers synchronously with a PLC-5 family processor.
Asynchronous block transfers do not work with this configuration and
cause the backplane circuit within the module to lock up. The BASIC
module ships with JW5 configured for 8-point mode (Series A
compatible). Unless you are using calls 32, 33, 34, 49, 50, 118, 122, or
123 (see Chapters 12 and 13) you should be in 8 point mode.
Important: You cannot use 2-slot chassis addressing if JW5 is set for 16
point mode. See page 1 -10 for information regarding the backplane
configuration and addressing.