Rockwell Automation 1771-DB BASIC MODULE User Manual
Page 289
Advertising
![background image](/manuals/579953/289/background.png)
Chapter
Call Routines 69–127
13
13 -31
Syntax
PUSH
remote device node address
PUSH
starting element offset (x2) of remote device file
PUSH
number of words to be transferred
PUSH
message time-out value
CALL 93
POP
status of message instruction
Example
>1 REM EXAMPLE PROGRAM
>30 PUSH 1 : REM REMOTE NODE ADDRESS = 1
>40 PUSH 0 : REM OFFSET = 0
>50 PUSH 10 : REM WORD LENGTH = 10
>60 PUSH 5 : REM THE TIME-OUT VALUE = 0.5 SECONDS
>70 CALL 93 : REM WRITE DATA FROM BASIC OUTPUT BUFFER
>80 POP R : REM GET THE OUTPUT ARGUMENT
>90 IF R<>0 THEN PRINT READ ERROR CODE = ”,R
READY
>RUN
READ ERROR CODE = 5
Advertising