Output Argument One
The output argument specifies the status of the message instruction.
Upon return from the call, the output argument has this definition:

Decimal
output

Hexadecimal
output

Description

0

00

successful completion

2

02

target node cannot accept the message at this time

3

03

target node cannot respond because message is too
large

4

04

target node cannot respond because it does not
understand the command parameters

5

05

BASIC module is off-line (not on link)

6

06

target node cannot respond because requested function
is not available

7

07

target node does not respond

10

0A

BASIC module detects illegal target node address

11

0B

BASIC module detects illegal file number

12

0C

BASIC module detects illegal target file element offset

13

0D

BASIC module detects illegal target file length

14

0E

BASIC module detects illegal time-out value

16

10

target node cannot respond because of incorrect
command parameters or unsupported command

55

37

message timed out (time-out value exceeded)

80

50

target node is out of memory

96

60

target node cannot respond because file is protected

231

E7

target node cannot respond because length requested
is too large

235

EB

target node cannot respond because target node denies
access

236

EC

target node cannot respond because requested function
is currently unavailable

241

F1

BASIC module detects illegal target file type

250

FA

target node cannot respond because another node is
file owner (has sole file access)

251

FB

target node cannot respond because another node is
program owner (has sole access to all files)