Rockwell Automation 1771-DB BASIC MODULE User Manual

Page 279

Advertising
background image

Chapter
Call Routines 69–127

13

13 -21

Syntax

PUSH

remote device node address

PUSH

remote device file number

PUSH

remote device file type

PUSH

starting element offset (x2) of remote device file

PUSH

number of elements to be transferred

PUSH

message time-out value

CALL 90

POP

status of message instruction

Example

>10 PUSH 1 : REM REMOTE NODE ADDRESS = 1

>20 PUSH 5 : REM REMOTE FILE 5

>30 PUSH ASC(C) : REM FILE TYPE = COUNTER

>40 PUSH 0 : REM OFFSET = 0

>50 PUSH 10 : REM ELEMENT LENGTH = 10 = 30 WORDS

>60 PUSH 5 : REM TIME-OUT = 0.5 SECONDS

>70 CALL 90

>80 POP R : REM GET THE OUTPUT ARGUMENT

>90 IF (R<>0) THEN PRINT “READ ERROR CODE =”,R

READY

>RUN

READ ERROR CODE = 5

Advertising