Chapter
Call Routines 0–68

12

12 -48

Input Argument Eight
The eighth input argument is the selection of the BTR buffer and/or string:

0

=

BTR

buffer

2 = internal string
4 = BTR buffer and internal string

If you choose internal string (2), you can execute CALL 29 (page 12 -18)
to initiate each data transfer without requiring PLC processor interaction.

Input Argument Nine
The ninth input argument is always 1.

Input Argument Ten
The tenth input argument is the string number. If the eighth input
argument does not select internal string usage, the value of this input
argument is ignored, but you must still PUSH it.

Output Argument One
The output argument is the status of the call. It has these values:

0 = successful
1 = disabled
2 = bad input parameter
3 = port DH-485 not enabled (DF1 enabled)
4 = string is too small
5 = string is not dimensioned
6 = JW5 not in 16-point position

Whenever an attempt is made to read a remote packet, the status of the
read is placed into BTR word 1. These values have the same definition as
the output values in CALL 92 (page 13 -26). The status becomes valid
when the BASIC module sets the input image table bit 14.

Syntax

PUSH

type of DH-485 READ command

PUSH

remote node address

PUSH

remote file number

PUSH

remote file type

PUSH

starting word offset of remote file

PUSH

number of words to be transferred

PUSH

message time-out value

PUSH

selection of destination file (BTR buffer)

PUSH 1

PUSH

string number

CALL 49

POP

CALL 49 status