Rockwell Automation 1771-DB BASIC MODULE User Manual

Page 283

Advertising
background image

Chapter
Call Routines 69–127

13

13 -25

Syntax

PUSH

remote device node address

PUSH

remote device file number

PUSH

remote device file type

PUSH

starting element offset (x2) of remote device file

PUSH

number of elements to be transferred

PUSH

message time-out value

CALL 91

POP

status of message instruction

Example

>1 REM EXAMPLE PROGRAM

>10 PUSH 1 : REM REMOTE NODE ADDRESS = 1

>20 PUSH 7 : REM REMOTE FILE 7

>30 PUSH ASC(N) : REM FILE TYPE = INTEGER

>40 PUSH 0 : REM OFFSET = 0

>50 PUSH 10: REM WORD LENGTH = 10

>60 PUSH 5 : REM THE TIME-OUT VALUE = 0.5 SECOND

>70 CALL 91 : REM WRITE DATA FROM OUTPUT BUFFER

>80 POP R : REM GET THE OUTPUT ARGUMENT

>90 IF R<>0 PRINT “READ ERROR CODE =”,R

READY

>RUN

READ ERROR CODE = 5