Rockwell Automation 1771-DB BASIC MODULE User Manual
Page 283
Advertising
![background image](/manuals/579953/283/background.png)
Chapter
Call Routines 69–127
13
13 -25
Syntax
PUSH
remote device node address
PUSH
remote device file number
PUSH
remote device file type
PUSH
starting element offset (x2) of remote device file
PUSH
number of elements to be transferred
PUSH
message time-out value
CALL 91
POP
status of message instruction
Example
>1 REM EXAMPLE PROGRAM
>10 PUSH 1 : REM REMOTE NODE ADDRESS = 1
>20 PUSH 7 : REM REMOTE FILE 7
>30 PUSH ASC(N) : REM FILE TYPE = INTEGER
>40 PUSH 0 : REM OFFSET = 0
>50 PUSH 10: REM WORD LENGTH = 10
>60 PUSH 5 : REM THE TIME-OUT VALUE = 0.5 SECOND
>70 CALL 91 : REM WRITE DATA FROM OUTPUT BUFFER
>80 POP R : REM GET THE OUTPUT ARGUMENT
>90 IF R<>0 PRINT “READ ERROR CODE =”,R
READY
>RUN
READ ERROR CODE = 5