Input and output arguments – Rockwell Automation 1771-DB BASIC MODULE User Manual

Page 276

Advertising
background image

Chapter
Call Routines 69–127

13

13 -18

Use CALL 90 to read up to 40 words from the designated node address,
file number, file type, and element offset of a remote DH-485 data file to
the BASIC module input buffer starting at word 100.

Input and Output Arguments

This routine has six input arguments and one output argument.

Argument

Description

Page

input 1

node address of the remote device (0–31)

13 -18

input 2

file number of the remote device (0–255) to be read

13 -18

input 3

file type read from the remote device

13 -18

input 4

starting element offset within the file on the remote
device (0 to 32767)

13 -19

input 5

number of elements to be transferred

13 -19

input 6

message time-out value

13 -19

output 1

call status

13 -20

Input Argument One
The first input argument is the node address of the remote device (0 to 31).
If the number is not within the range 0 to 31, then the output argument
equals 10, and the read message does not take place.

Input Argument Two
The second input argument is the file number on the remote device (0 to
255) to be read. If the number is not within the range 0 to 255, then the
output argument equals 11, and the read message does not take place.

Input Argument Three
The third input argument is the file type read from the remote device.
If the file type is not one of the valid types listed in the table, then the
output argument equals 241, and the read message does not take place.

File type

File type code

Words/Element

integer file

ASC(N)

1 word/element

status file

ASC(S)

1 word/element

counter file

ASC(C)

3 words/element

timer file

ASC(T)

3 words/element

bit file

ASC(B)

1 word/element

control file

ASC(R)

3 words/element

CALL 90: Read Remote