Rockwell Automation 1771-DB BASIC MODULE User Manual

Page 331

Advertising
background image

Chapter
Call Routines 69–127

13

13 -73

Indicates

Code

D5

data conversion error

D6

the scanner is not able to communicate with a 1771 chassis
adapter

D7

the adapter is not able to communicate with the module

D8

the 1771 module response was not valid

D9

duplicated label

DA

file is open – another station owns it

DB

another station is the program owner

Syntax

PUSH

type of PLC WRITE command

PUSH

remote PLC node address

PUSH

file number of remote PLC

PUSH

file type on remote PLC

PUSH

starting word offset on remote PLC

PUSH

number of elements to be transferred

PUSH

message time-out value

PUSH

selection of BTW buffer or internal string

PUSH 1

PUSH

string number

CALL 123

POP

CALL 123 status

Example

>15 PUSH 64: CALL 4: REM SET BLOCK TRANSFER WRITE LENGTH

>16 PUSH 64: CALL 5: REM SET BLOCK TRANSFER READ LENGTH

>20 PUSH 5 : REM PLC-5 FILE

>30 PUSH 0 : REM PLC-5 NODE ADDRESS

>40 PUSH 7 : REM PLC-5 FILE NUMBER

>50 PUSH ASC(N) : REM PLC-5 FILE TYPE

>60 PUSH 0 : REM STARTING WORD OFFSET FOR PLC-5

>70 PUSH 20 : REM NUMBER OF WORDS TO TRANSFER

>80 PUSH 10 : REM COMMAND TIME-OUT VALUE (X100MS)

>90 PUSH 0 : REM USE BTW BUFFER

>100 PUSH 1 : REM ALWAYS 1

>110 PUSH 0 : REM STRING NUMBER–NA FOR THIS EXAMPLE

>120 CALL 123

>130 POP S : REM STATUS OF THE CALL

>140 IF (S<>0) THEN PRINT “UNSUCCESSFUL CALL 123 SETUP”