Rockwell Automation Publication 7000-IN007E-EN-P - June 2014

13

PowerFlex 7000 Overview

Chapter 2

Figure 2 - 3300/4160V AFE Rectifier (Direct-to-Drive)

AFE Rectifier with Separate Isolation Transformer

For applications when the line voltage is higher than the motor voltage, a
transformer is required for voltage matching. In this case, providing an AFE
rectifier with a separate isolation transformer is ideal. The isolation transformer
provides the input impedance (replaces the requirement for an integral line
reactor) and addresses the common mode voltage (replaces the requirement for a
CMC that is supplied in the Direct-to-Drive rectifier configuration). However,
the AFE rectifier, its operation, and advantages are the same as the Direct-to-
Drive configuration.

Figure 3 - 3300/4160 AFE Rectifier with separate isolation transformer)

SGCTs

LINE CONVERTER

OMMON MODE CHOKE

C

L+

M+

SGCTs

MACHINE CONVERTER

U (T1)

V (T2)

W (T3)

L-

M-

LR

SGCTs

LINE CONVERTER

DC LINK

L+

M+

SGCTs

MACHINE CONVERTER

U (T1)

V (T2)

W (T3)

L-

M-

REMOTE
ISTX

2U (X1)

2V (X2)

2W (X3)

1U

1V

1W