Rockwell Automation 7000 PowerFlex Medium Voltage Air-Cooled (B Frame) Installation - ForGe Control User Manual

Page 76

Advertising
background image

76

Rockwell Automation Publication 7000-IN007E-EN-P - June 2014

Appendix A

General Reference

PowerFlex 7000 Drive
Performance (Torque
Capabilities)

The PowerFlex 7000 drives have been tested on a dynamometer to verify
performance under locked rotor, accelerating, and low speed-high torque
conditions.

Table 13

shows the PowerFlex 7000 drive torque capabilities as a

percent of motor rated torque, independent of the drive’s momentary overload
conditions.

Table 13 - PowerFlex 7000 Drive Torque Capabilities

Standard Control Mode

3600

600

3000

600

1800

1024

1500

1024

1200

2048

1000

2048

900

2048

720

2048

600

2048

Table 12 - Encoder Selection (Continued)

Parameter

7000 Torque Capability
without Encoder (% of
Motor Rated Torque)

7000 Torque Capability
with Encoder (% of
Motor Rated Torque)

7000 Torque Capability with
Encoder and High Performance
Torque Control (HPTC)

Breakaway Torque

90%

150%

150%

Accelerating Torque

90% (0...8 Hz)

140% (0...8 Hz)

150% (0...75 Hz)

125% (9...75 Hz)

140% (9...75 Hz)

Steady State Torque

125% (9...75 Hz)

(1)

100% (1...2 Hz)

150% (0...60 Hz)

(1)

140% (3...60 Hz)

(1)

(1) Drive will require over-sizing to achieve greater than 100% continuous torque.

Max. Torque Limit

150%

150%

150%