D - specifications, Appendix d, Specifications – Rockwell Automation 7000 PowerFlex Medium Voltage Air-Cooled (B Frame) Installation - ForGe Control User Manual

Page 91: Appendix

Advertising
background image

Rockwell Automation Publication 7000-IN007E-EN-P - June 2014

91

Appendix

D

Specifications

Specifications

ATTENTION: In the event of discrepancies between information published in
generic manual specifications and those included with your specific design or
electrical drawings, take the DD or EE ratings as correct values.

Table 16 - General Design Specifications

Description

Motor Type

Induction or Synchronous

Input Voltage Rating

2400V, 3300V, 4160V, 6600V

Input Voltage Tolerance

± 10% of Nominal

Voltage Sag

(1)

-30%

Control Power Loss Ride-through

5 Cycles (Std)
> 5 Cycles (Optional UPS)

Input Protection

(2)

Surge Arrestors (AFE/Direct-to-Drive)
Metal Oxide Varistor (MOV) (18 Pulse)

Input Frequency

50/60 Hz, +/- 0.2%

Power Bus Input Short-circuit
Current Withstand (2400…6600V

(3)

)

25 kA RMS SYM, 5 Cycle

Basic Impulse Level

(4)

45 kV (0…1000 m)

Power Bus Design

Copper - Tin plated

Ground Bus

Copper - Tin plated 6 x 51 mm (¼ x 2 in.)

Customer Control Wire Way

Separate and Isolated

Input Power Circuit Protection

(5)

Vacuum Contactor with Fused Isolating Switch
or Circuit Breaker

Output Voltage

0…2400V
0…3300V
0…4160V
0…6000V, 0…6300V, 0…6600V

Inverter Design

PWM

Inverter Switch

SGCT

Inverter Switch Failure Mode

Non-rupture, Non-arc

Inverter Switch Failure Rate (FIT)

100 per 1 Billion Hours Operation

Inverter Switch Cooling

Double Sided, Low Thermal Stress

Inverter Switching Frequency

420…440 Hz

Advertising