Meggering procedures, Required equipment, Procedure – Rockwell Automation 7000 PowerFlex Medium Voltage Air-Cooled (B Frame) Installation - ForGe Control User Manual

Page 80: Required equipment procedure

Advertising
background image

80

Rockwell Automation Publication 7000-IN007E-EN-P - June 2014

Appendix B

Meggering

Following this procedure to perform Megger tests on the PowerFlex 7000B.
Failure to comply with this procedure may result in poor Megger reading and
damage to drive control boards.

Meggering Procedures

Required Equipment

Torque Wrench and 7/16 in. socket

Phillips Screwdriver

2500/5000V Megger

Procedure

1.

Isolate and lock out the drive system from any high voltage source.

Disconnect any incoming power sources, medium voltage sources should
be isolated and locked out and all control power sources should be turned
off at their respective circuit breaker(s).

Verify with a potential indicator that power sources have been
disconnected, and that the control power in the drive is de-energized.

2.

Isolate the power circuit from system ground (“float the drive”).

Remove the grounds on the following components within the drive (refer
to the electrical diagrams provided with the equipment to assist in
determining the points to disconnect):

Voltage Sensing Boards (VSB)

Output Grounding Network (OGN)

Voltage Sensing Boards

a. Remove all ground connections from all of the VSBs in the drive. Do

this at the screw terminals on the VSB rather than the ground bus.
There are two grounds on each board marked “GND 1”, and “GND 2”.

Note: It is important to disconnect the terminals on the boards rather
than from the ground bus as the grounding cable is only rated for 600V.
Injecting a high voltage on the ground cable will degrade the cable
insulation. Do not disconnect the white medium voltage wires from the
VSBs. They must be included in the test.

The number of VSBs installed in each drive varies depending on the
drive configuration.

Advertising