Rockwell Automation Publication 7000-IN007E-EN-P - June 2014

Chapter 3

Drive Installation

Even if the shock indicators are clear, perform a full equipment inspection and
verification. Refer to

Pre-Commissioning Responsibilities on page 65

for details

on the inspection and verification process.

Figure 31 - Shock Indicator

Joining Shipping Splits
(3300...4160V and 6600V
Heat Pipe Model)

The 3300...4160 and 6600V heat pipe drives are the “B” Frame models that ship
in multiple sections (two for 3300...4160V and three for 6600V). All other “B”
Frame models ship as a single unit. For the 3300...4160V heat pipe model, the
choke section ships separately from main section of the drive (

Figure 32

). For the

6600V heat pipe model, the choke cabinet and the line reactor section ship
separately from the main section of the drive (

Figure 33

)

Arrange the sections as directed in the dimension drawings and move the sections
together. Join the enclosure’s side sheets with thread-forming screws using the
available holes.

Complete ground bus, power, and control connections as directed in the
electrical diagrams and this installation guide.

Red Plastic Housing

Window Area appears black

if subjected to shock

51 mm

(2.0)

21 mm

(0.8)

IMPORTANT

Refer to publication

7000-IN008_-EN-P

for details regarding moving and

siting the drive before continuing with these installation procedures.

ATTENTION: Install the drive on a level surface (+/- 1 mm over the length of
the drive). Use metal shims if necessary to level the cabinets before joining
them; attempting to level after joining may result in twisting the cabinets.