62

Rockwell Automation Publication 7000-IN007E-EN-P - June 2014

Chapter 3

Drive Installation

Grounding Practices

Grounding:

increases personnel safety

limits dangerous voltages on exposed parts with respect to ground

facilitates proper over-current device operation under ground fault
conditions, and

provides electrical interference suppression

Generally, all external equipment grounding should meet the Canadian Electrical
Code (CEC) C22.1, or the NEC NFPA 70, and applicable local codes.

Refer to the following diagrams for ground connections. Do not connect the
drive’s main ground bus to the system ground. This ground bus is the common
ground point for all grounds internal to the drive.

Figure 54 - Ground connection diagram with isolation transformer

Figure 55 - Ground connection diagram with line reactor

Provide each power feeder from the substation transformer to the drive with
properly sized ground cables. Using conduit or cable armor as a ground on its
own is insufficient. Note that if you use a drive isolation transformer, do not
ground the WYE secondary neutral point.

Bond each AC motor frame to grounded building steel within 6 m (20 ft) of its
location and tie it to the drive's ground bus via ground wires within the power
cables and/or conduit. The conduit or cable armor should bond to ground at
both ends.

ISOLATION

TRANSFORMER

AC

MOTOR

U (T1)

V (T2)

W (T3)

2U

2V

2W

GROUND BUS

Connected to the neutral point
of the output capacitor

OUTPUT

GROUND

NETWORK

ISOLATION

TRANSFORMER

AC

MOTOR

U (T1)

V (T2)

W (T3)

2U

2V

2W

GROUND BUS

Connected to the neutral point
of the output capacitor

OUTPUT

GROUND

NETWORK

AC

MOTOR

U (T1)

V (T2)

W (T3)

2U

2V

2W

GROUND BUS

AC LINE

REACTOR

TRANSFORMER

Connected to the neutral point
of the output capacitor

GROUND

FILTE R

AC

MOTOR

U (T1)

V (T2)

W (T3)

2U

2V

2W

GROUND BUS

AC LINE

REACTOR

TRANSFORMER

Connected to the neutral point
of the output capacitor

GROUND

FILTE R