Rockwell Automation Publication 7000-IN007E-EN-P - June 2014
69
Pre-Commissioning Responsibilities
Chapter 4
Table 10 - Drive Line-up Status
All power connections are torqued as per Rockwell
Automation specifications. Refer to
for Threaded Fasteners on page 73
.
All customer power cabling has been meggered or hi-pot
tested before connecting to drive system.
Power wiring phase rotation has been verified per the
specific electrical diagrams supplied by Rockwell
Automation.
Initials
Date
Check
The medium voltage and low voltage power is available
for startup activities.
The motor is uncoupled from the driven load.
The load is available for full load testing.
Initials
Date
Check