Drive Installation
Chapter 3
Terminating Customer Cables
Customer termination assemblies can accommodate either top or bottom
customer cable entry. For clarity,
three; there are a total of nine lug pads.
Figure 52 - Typical Line Cable Termination (shown assembled for bottom cable entry – 18 Pulse)
For top line cable entry, remove the lug pads and re-orient them as shown in
. To remove the lug pads, disconnect the M10 bus connection hardware
(17 mm hex tooling required). Remove the two bolts that secure the lug pad to
the 4-hole insulator. Refer to
Torque Requirements for Threaded Fasteners on
for more information regarding these electrical connections.
Figure 53 - Typical Line Cable Terminal Assembly (modified for top cable
entry – 18 Pulse)
4-hole insulator
Bolts
Customer supplied lugs
4 lugs per phase maximum
M10 bus connection
hardware
Lug pad shown with
bottom cable entry
orientation
Lug pad oriented
for top cable entry