Rockwell Automation Publication 7000-IN007E-EN-P - June 2014

61

Drive Installation

Chapter 3

Terminating Customer Cables

Customer termination assemblies can accommodate either top or bottom
customer cable entry. For clarity,

Figure 52

and

Figure 53

show only one phase of

three; there are a total of nine lug pads.

Figure 52 - Typical Line Cable Termination (shown assembled for bottom cable entry – 18 Pulse)

For top line cable entry, remove the lug pads and re-orient them as shown in

Figure 53

. To remove the lug pads, disconnect the M10 bus connection hardware

(17 mm hex tooling required). Remove the two bolts that secure the lug pad to
the 4-hole insulator. Refer to

Torque Requirements for Threaded Fasteners on

page 73

for more information regarding these electrical connections.

Figure 53 - Typical Line Cable Terminal Assembly (modified for top cable
entry – 18 Pulse)

4-hole insulator

Bolts

Customer supplied lugs
4 lugs per phase maximum

M10 bus connection
hardware

Lug pad shown with
bottom cable entry
orientation

Lug pad oriented
for top cable entry