C - line & load cable sizes, Max. line cable sizes, Appendix c – Rockwell Automation 7000 PowerFlex Medium Voltage Air-Cooled (B Frame) Installation - ForGe Control User Manual

Page 85: Line & load cable sizes, Appendix

Advertising
background image

Rockwell Automation Publication 7000-IN007E-EN-P - June 2014

85

Appendix

C

Line & Load Cable Sizes

Max. Line Cable Sizes

PRODUCT

INPUT (LINE SIDE)

Bulletin

Description

(V/Freq./Rect.)

Drive

rating (A)

Drive Structure Code

Drive Enclosure Opening

Inches (mm)

1

Max. Size & No. Incoming

Cables:

NEMA

2-4-5-6-8-9

Max. Size & No.

Incoming Cables:

IEC

2-4-5-6-8-9

Vertical Space

Avail. for

Stress Cones
Inches (mm)

‘A’ Frame
(Air-
Cooled)

PF7000A

2400V/60Hz/RPDTD

46...140

71.9 w/ starter

4.00x4.00 (102x102)

(1) #4/0 5 kV or
8 kV/phase

(1) 107mm² 5 kV
or 8 kV/phase

18.8 (478)

PF7000A

2400V/60Hz/RPDTD

46...140

71.13, 71.18 w/o starter

4.00x4.00 (102x102)

(1) #4/0 5 kV or
8 kV/phase

(1) 107mm² 5 kV
or 8 kV/phase

17.1 (435)

PF7000A

3300V/50Hz/RPDTD

46...140

71.9 w/ starter

4.00x4.00 (102x102)

(1) #4/0 5 kV or
8 kV/phase

(1) 107mm² 5 kV
or 8 kV/phase

18.8 (478)

PF7000A

3300V/50Hz/RPDTD

46...140

71.13, 71.18 w/o starter

4.00x4.00 (102x102)

(1) #4/0 5 kV or
8 kV/phase

(1) 107mm² 5 kV
or 8 kV/phase

17.1 (435)

PF7000A

4160V/50Hz/RPDTD

46...140

71.9 w/ starter

4.00x4.00 (102x102)

(1) #4/0 5 kV or
8 kV/phase

(1) 107mm² 5 kV
or 8 kV/phase

18.8 (478)

PF7000A

4160V/50Hz/RPDTD

46...140

71.13, 71.18 w/o starter

4.00x4.00 (102x102)

(1) #4/0 5 kV or
8 kV/phase

(1) 107mm² 5 kV
or 8 kV/phase

17.1 (435)

PF7000A

4160V/60Hz/RPDTD

46...140

71.9 w/ starter

4.00x4.00 (102x102)

(1) #4/0 5 kV or
8 kV/phase

(1) 107mm² 5 kV
or 8 kV/phase

18-3/8 (467)

PF7000A

4160V/60Hz/RPDTD

46...140

71.13, 71.18 w/o starter

4.00x4.00 (102x102)

(1) #4/0 5 kV or
8 kV/phase

(1) 107mm² 5 kV
or 8 kV/phase

17.1 (435)

PF7000A

6600V/50Hz/RPDTD

40...93

71.10 w/ starter

4.00x4.00 (102x102)

(1) #4/0 8 kV or
15 kV/phase

(1) 107mm² 5 kV
or 8 kV/phase

18.8 (478)

PF7000A

6600V/50Hz RPDTD

40...93

71.14, 71.19 w/o starter

4.00x4.00 (102x102)

(1) 350MCM
8 kV or 15 kV/phase

(1) 177mm² 8 kV
or 15 kV/phase

17.1 (435)

PF7000A

2400V/60Hz/RPTX

46...160

71.7

4.00x8.00 (102x204)

1

(1) 350MCM
8 kV or 15 kV/phase

(1) 177mm² 5 kV
or 8 kV/phase

33.8 (860)

PF7000A

3300V/50Hz/RPTX

46...160

71.7

4.00x8.00 (102x204)

1

(1) 350MCM
8 kV or 15 kV/phase

(1) 177mm² 8 kV
or 15 kV/phase

33.8 (860)

PF7000A

4160/50Hz/RPTX

46...160

71.7

4.00x8.00 (102x204)

1

(1) 350MCM
8 kV or 15 kV/phase

(1) 177mm² 8 kV
or 15 kV/phase

33.8 (860)

PF7000A

4160/60Hz/RPTX

46...160

71.7

4.00x8.00 (102x204)

1

(1) 350MCM
8 kV or 15 kV/phase

(1) 177mm² 8 kV
or 15 kV/phase

33.8 (860)

PF7000A

6600/50Hz/RPTX

40...105

71.8

4.00x8.00 (102x204)

1

(1) 350MCM
15 kV/phase

(1) 177mm²
15 kV/phase

33.8 (860)

PF7000A

2400V/60Hz/RPTXI

46...160

71.3

4.00x4.00 (102x102)

(1) 350MCM
8 kV or 15 kV/phase

(1) 177mm² 5 kV
or 8 kV/phase

20.0 (508)

3

PF7000A

3300V/50Hz/RPTXI

46...160

71.3

4.00x4.00 (102x102)

(1) 350MCM
8 kV or 15 kV/phase

(1) 177mm² 5 kV
or 8 kV/phase

20.0 (508)

3

PF7000A

4160V/50Hz/RPTXI

46...140

71.3

4.00x4.00 (102x102)

(1) 350MCM
8 kV or 15 kV/phase

(1) 177mm² 5 kV
or 8 kV/phase

20.0 (508)

3

PF7000A

4160V/60Hz/RPTXI

46...160

71.3

4.00x4.00 (102x102)

(1) 350MCM
8 kV or 15 kV/phase

(1) 177mm² 5 kV
or 8 kV/phase

20.0 (508)

3

PF7000A

6600V/50Hz/RPTXI

40...105

71.6, 71.15

4.00x4.00 (102x102)

(1) #4/0 8 kV or
15 kV/phase

(1) 177mm² 8 kV
or 15 kV/phase

20.0 (508)

3

Advertising