Testing the network for data transmission – Rockwell Automation 2708-DH5B2L_DH5B4L Attended Workstation User Manual

Page 23

Advertising
background image

Chapter 2

Installing a Network

2–10

1. At the LAST workstation in the network, place the workstations into the

menu setup mode (see Appendix B).

a. Press the left arrow key (<) until the Diagnostic menu statement

appears in the display.

b. Press the ENTER key and then depress the left arrow key (<) until

RS-485 – BLK-Rx is shown on the display.

c. Press the ENTER key and the following should appear:

Rx = 00000

ERRS = 00

000

If the counters are not zero, press EXIT, then press ENTER, and they
should be set to zero.

d. Repeat steps a, b, and c for all workstations, except the Master

workstation.

2. At the Master workstation enter the Diagnostic menu and press the left

arrow key (<) until RS-485 – BLK-Tx is shown on the display.

a. Press ENTER and the display should show the following,

momentarily:

Tx = 00000

ERRS = 00

000

After the counters appear, the Tx counter will begin incrementing to
represent the number of blocks being transmitted over the network to all
workstations.

b. An observation of the display of the workstations placed in receive

will show the Rx counter changing accordingly as the transmitted
network blocks are received.

c. After a reasonable testing interval, press the EXIT key on the

Master workstation, thus suspending the network block test.

d. Examine each workstation to see that the Rx block count is the

same. It should be the same at all workstations (It is possible to be
off by one or two counts.) Also, inspect to see that ERRS count is
zero or less than three. Either a missing block count or high error
count indicates a bad network connection or a faulty workstation.
Exchanging the workstation will determine which is the case.

e. For additional confidence, perform step 1 at the Master workstation

location and step 2 at the last location. Step 1 may be repeated at all
other workstations. The changing of block transmission locations
verifies communications in the opposite direction.

f. Press EXIT three times on each workstation.

3. Always use retaining screws for all DB-9 connectors. Connect the RS-232

(or RS-422) cable to the host computer.

Testing the Network for
Data Transmission