Error Messages

A-3

Download cannot be opened. The drive is busy.
The drive is performing another operation. Wait a short amount of time and attempt
the operation again.

Download cannot be performed. A network card is the control source.
Change the control source from the drive keypad to perform a download.

Variable processing errors occurred in the drive.
The drive had to change parameter values after a download was completed.

Parameter write errors occurred during download.
Some parameter values could not be written to the drive. This error indicates a
problem in the CS3000 software or drive.

Parameter write attempted to a configurable parameter while drive is running.
Configurable parameters cannot be changed while the drive is running. The drive
must be stopped to perform the intended operation.

Parameter value is out of range.
A parameter write was attempted with an out of range value.

Parameter could not be found in the drive.
The CS3000 software attempted to read the value of a parameter that is not in the
drive.

The number of parameters in read is invalid.
The read request to the drive was invalid.

Read attempted with invalid parameter index.
The CS3000 software attempted to read a parameter that does not exist in the drive.

Invalid read message format.
The read message format created by the CS3000 software is invalid.

COM port is not available.
The selected COM port is not installed in the PC or is being used by a DOS
application, such as the mouse driver.

COM port is being used by another application.
The selected COM port is being used by another Windows application.

Unable to read signal trace information from drive.
The CS3000 software could not read the information from the drive needed for the PC
Scope. Check the drive connection.

Sample rate not supported.
Under some conditions in a drive, a sample rate may not be available for a PC Scope
signal. Change the sample rate.

Failed to create status bar.
This error may be caused by a lack of memory. Close the application and retry.

Could not create toolbar.
This error may be caused by a lack of memory. Close the application and retry.