Generating a fuzzy add-on instruction – Rockwell Automation RSLogix 5000 Fuzzy Designer User Manual

Page 134

Advertising
background image

Publication LOGIX-UM004A-EN-P - March 2007

134 RSLogix 5000 Add-On Instruction

Generating a Fuzzy Add-On
Instruction

You can export a fuzzy system to an Add-On Instruction XML import
file (.L5X).

To generate the Add-On Instruction (AOI) for the active fuzzy project,
click Tools>Add-On Instruction > Instruction Generator.

The following dialog appears.

The following conditions must be met to generate a fuzzy AOI:

• All blocks of the fuzzy system must be connected

• The fuzzy system must include at least one input port and one

output port

• All rules must be complete (there is no rule with empty

conditions or consequents)

• Each rule block must include at least one rule

• Each linguistic variable must include at least one term

The default file name of the Add-On Instruction is taken from the
name of the fuzzy system in FuzzyDesigner, but you can change the
name. The instruction name must follow to the Add-On Instruction
naming rules. It must:

• Be no more than 40 characters long.
• Start with a letter or underscore (_). All other characters can be

letters, numbers, or underscores.

Advertising