Demo Unit User Manual (AADvance Controller)

1-10

Document: 553850 Issue 1.2: March 2011

T9401/2 Digital Input Module, 24V dc, 8/16 channel

The T9401/2 digital input module monitors eight (T9401) or

sixteen (T9402) isolated digital input channels and notifies the
processor module of each field device state and channel

condition. Each channel provides both digital state and analogue

voltage data to the processor module for field device state, line

monitoring and field fault detection.

The input module provides local module and channel status

indications through its front panel LEDs, the same indications

can be connected to application variables and viewed at the
Workbench. Comprehensive diagnostics at both system and

module levels generate clear fault indications which help rapid

maintenance and repair.

The module incorporates signal and power isolation circuits,
which separate each input channel from the rest of the system,

protecting the controller from field faults. An independent

watchdog arrangement monitors the module operation and

provides additional fault containment by a shutdown mechanism
should a fault occur.

When a controller uses a digital input module in a dual or TMR

configuration, plant maintenance personnel can fit a new input
module without interrupting the input signals.

Digital Input Line Monitoring

Each digital input module parameters is set up through the AADvance Workbench
configuration tools. Switching levels for each digital input channel are configurable at

the module and the channel level. Each input has five configurable voltage bands (there
are eight distinct switching thresholds to allow hysteresis), each of which can be

adjusted through the AADvance Workbench to provide line monitoring, field loop
monitoring and additional field device diagnostics.

Advertising