Rockwell Automation AADvance Controller Demo Unit User Manual

Page 99

Advertising
background image

Document: 553850 Issue 1.2: March 2011

5-33

Field Power Status Integers

The variables in the rack of field power status integers (all DINT) provide information

to the application about the field power supplies to a group of digital output modules.

Group Field Power Current

Direction: input to application from controller
Type: DINT
Values:



0 to 8,000mA or greater (limited by capacity of DINT variable)

Description:
Reports the total current that all the active digital output modules in a group are
drawing from the field power supply. Accuracy is ± 10%.

A Module Field Power Voltage 1

Direction: input to application from controller
Type: DINT
Values:



0 to 48,000mV or greater (limited by capacity of DINT variable)

Description:
Reports the voltage from the field power supply, for the specified module and field
power input. Accuracy is ± 500mV.

A Module Field Power Voltage 2

Direction: input to application from controller
Type: DINT
Values:



0 to 48,000mV or greater (limited by capacity of DINT variable)

Description:

Reports the voltage from the field power supply, for the specified module and field
power input. Accuracy is ± 500mV.

B Module Field Power Voltage 1

Direction: input to application from controller
Type: DINT
Values:



0 to 48,000mV or greater (limited by capacity of DINT variable)

Description:
Reports the voltage from the field power supply, for the specified module and field
power input. Accuracy is ± 500mV.

Advertising