Wire Variables to Analogue Input Channels

To wire variables to analogue input channels do the following:

1) Select an analogue input module on the I/O bus.



The module status variable <tagname> that you assigned will appear in the
Variable field.

2) Select the channel that you want to wire to a variable.

3) Click the button next to the channel variable fields.
4) Choose a data structure from the three options displayed: Simple, Compact,

Full.



The Select Variables dialog box is displayed.

5) Select a named structure, click OK.
6) Repeat steps 2 to 5 for each channel.