Rockwell Automation AADvance Controller Demo Unit User Manual

Page 19

Advertising
background image

Document: 553850 Issue 1.2: March 2011

1-13

T9451 Digital Output Module Specification

Table 3:

T9451 Digital Output Module Specification

Attribute Value

Functional Characteristics

Number of output channels

8 per module

Degradation 1oo1D,

1oo2D

Performance Characteristics

Safety integrity level

IEC 61508 SIL3

Self-test interval

<30 mins (30s per module)

Electrical Characteristics

Supply Voltage

Redundant +24V dc nominal;

18V dc to 32V dc range

Output characteristics:

Operating field supply voltage

0V to +50V dc

Maximum voltage without damage

–1V to +60V dc

Nominal output voltage

+ 24V dc

Range

+ 18V to 32V dc

Output current

1A continuous per channel

Voltage Drop at Maximum Current

< 1volt (approximately 0.9V)

Max output current before shutdown

6 A @ 60°C for all channels

Output overload protection

Surge

10A for up to 50ms

Continuous

1.5A

Power consumption

Module power (from controller 24V supply)

2W

Channel Field power (from source of field power) 24W (up to 192W per module)

Total maximum power consumption

198W (all 8 channels 'on' at maximum

current)

Heat dissipation

6W per module

Mechanical Specification

Dimensions (height × width × depth)

166mm × 42mm × 118mm

(6-½ in. × 1-21/32 in. × 4-21/32 in.)

Weight

340g (12 oz.)

Casing

Plastic, non flammable