Rockwell Automation AADvance Controller Demo Unit User Manual

Page 51

Advertising
background image

Document: 553850 Issue 1.2: March 2011

4-17

Processor Module B On-line

Direction: input to application from controller
Type: boolean
Values:



TRUE = The 9110 processor module in the given slot is on-line



FALSE = The processor module is off-line



Default: TRUE

Description:
Reports that a processor module within a dual or triple modular redundant

configuration is present and is communicating through the inter-processor link to one
or both of its peers. Reports that a simplex processor module is present.

Processor Module C On-line

Direction: input to application from controller
Type: boolean
Values:



TRUE = The 9110 processor module in the given slot is on-line



FALSE = The processor module is off-line



Default: TRUE

Description:

Reports that a processor module within a dual or triple modular redundant
configuration is present and is communicating through the inter-processor link to one

or both of its peers. Reports that a simplex processor module is present.

Processor Module A Health

Direction: input to application from controller
Type: boolean
Values:



TRUE = The 9110 processor module in the given slot is healthy and its Healthy
LED indicator is green.



FALSE = The processor module is faulty and its Healthy LED indicator is red.

Description:
Reports the health status of a processor module.