Document: 553850 Issue 1.2: March 2011

4-21

Processor Module C Ready

Direction: input to application from controller
Type: boolean
Values:



TRUE = The 9110 processor module in the given slot is synchronized (see
description)



FALSE = The processor module is out of synchronization or missing.

Description:
Reports that a processor module within a dual or triple modular redundant
configuration is present and is synchronized with one or both of its peers. Reports that

a simplex processor module is present.

Processor Module A NVRAM Battery Health

Direction: input to application from controller
Type: boolean
Values:



TRUE = The back-up battery in the 9110 processor module in the given slot is
present and its voltage is within acceptable limits.



FALSE = The voltage of the back-up battery is low or the battery is missing.

Description:
Reports the health status of the back-up battery in a processor module.

Note: The battery voltage is checked at start up, then re-checked every 24 hours
(elapsed time).

Processor Module B NVRAM Battery Health

Direction: input to application from controller
Type: boolean
Values:



TRUE = The back-up battery in the 9110 processor module in the given slot is
present and its voltage is within acceptable limits.



FALSE = The voltage of the back-up battery is low or the battery is missing.

Description:
Reports the health status of the back-up battery in a processor module.

Note: The battery voltage is checked at start up, then re-checked every 24 hours
(elapsed time).