Document: 553850 Issue 1.2: March 2011

4-25

RTC Status: Milliseconds

Direction: input to application from controller
Type: word
Values:



0 to 999

Description:

Reports the oldest value of real-time clock (RTC) milliseconds as voted by every 9110
processor module which is present and synchronized. Only updated if the real-time

clock control Boolean RTC Read is set to TRUE. If RTC Read is FALSE, the value will
be 0 (zero).

RTC Program Variables

The variables in the rack of RTC program variables specify parts of the date to be
written to the real-time clock the next time the RTC control variable RTC Write is

asserted TRUE.

Note: The values will be written only if the RTC control variable Year is TRUE.

RTC Program: Year

Direction: output from application to controller
Type: word
Values:



2,000 to 2,399



Default 0 (zero)

Description:

Specifies the year part of the date to be written to the real-time clock the next time
the RTC control variable RTC Write is asserted TRUE. The value will be written
only if the RTC control variable Year is TRUE.

RTC Program: Month

Direction: output from application to controller
Type: word
Values:



1 to 12



Default 0 (zero)

Description:

Specifies the number of the month part of the date to be written to the real-time clock
the next time the RTC control variable RTC Write is asserted TRUE. The value will
be written only if the RTC control variable Month is TRUE.