Rockwell Automation AADvance Controller Demo Unit User Manual

Page 85

Advertising
background image

Document: 553850 Issue 1.2: March 2011

5-19

<tagname>.CNT

INT

Raw count

A count representing the current on the

channel in units of 1/256mA

0 represents 0mA; 5,120 represents 20mA

Accurate to within ± 13 counts, equivalent to

± 0.05mA

<tagname>.LF

BOOL

Line fault

TRUE: state (.STA) is 1, 5, 6 or 7

FALSE: state (.STA) is 2, 3 or 4

<tagname>.DIS BOOL

Discrepancy TRUE:

there is a discrepancy in current

greater than 2% between the channels of two
or three modules in a redundant configuration

(†)

<tagname>.CF

BOOL

Channel fault

TRUE: module diagnostics detect a fault in the

channel electronics or firmware (state = 7)

<tagname>.STA USINT

State

Reports

a state value for the channel:

1 = open circuit
2 = transmitter fault (low)
3 = normal
4 = transmitter fault (high)
5 = short-circuit
6 = over range
7 = faulted

Note: (†) Discrepancy can only be reported TRUE when two or three modules are
active in a group.

Faulted State for Analogue Inputs

An analogue input channel is faulted (the state reports a value of 7) when the channel

is incapable of reporting a count within a safety accuracy specification of 1% of the full
scale measurement range of 5,120 (51 counts, 0.2mA).
When the state reports the value 7 then the following 'safe' values are reported by the
other variables:



Process Value = a calculated value based on a Count value of 0



Line Fault = TRUE



Discrepancy = TRUE



Channel Fault = TRUE



Count = 0