Demo Unit User Manual (AADvance Controller)

5-22

Document: 553850 Issue 1.2: March 2011

<tagname>.DEVICE BYTE

Device status (†)

Bit 7: field device malfunction

Bit 6: configuration changed

Bit 5: cold start

Bit 4: more status available

Bit 3: analogue output current fixed

Bit 2: analogue output saturated

Bit 1: non-primary variable out of

limits

Bit 0: primary variable out of limits

Note: (†) The device status byte mimics the HART field device status. Appendix E of
the HART Application Guide gives details.

About Threshold Values for Analogue Inputs

The module determines the channel state and the line fault status by comparing the

channel input current with defined threshold values. You can define your own
threshold values or use a set of default values. The values you choose for the module
are inherited by each channel; you can define different thresholds for individual

channels later.
Thresholds are specified in counts, with 0 (zero) being 0mA, 1,024 being 4mA, and

5,120 being 20mA.

Note: When the system is operational you should change these values only using an
on-line update.

The AADvance controller provides hysteresis on the thresholds for increasing and

decreasing values to prevent chatter. The Workbench updates the reporting values
during every application cycle.