Rockwell Automation AADvance Controller Demo Unit User Manual

Page 94

Advertising
background image

Demo Unit User Manual (AADvance Controller)

5-28

Document: 553850 Issue 1.2: March 2011

Overcurrent Protection for Digital Outputs

The AADvance controller has three mechanisms to protect its digital output channels:



Inrush current protection



Short circuit protection for energized channels



Short circuit protection for de-energized channels

The controller tolerates inrush currents so that its digital outputs can energize

capacitive loads without causing the controller to report a short circuit. The
illustration shows the characteristics of the maximum load currents that the controller
will tolerate when a digital output is commanded on. If the load current enters the

region above the curve on the graph, the controller applies its inrush current
protection.

After allowing for inrush, the controller engages its short circuit protection for an

energized channel when the loop current reaches 2A.



Short circuit detection on an energized channel is immediate and the channel is de-
energized. The controller reports the condition until the short circuit is cleared.



When the short circuit is removed, the channel will re-energize. The short circuit
report is then cleared by pressing the fault reset button on the 9110 processor

module or by setting the commanded state is set to FALSE.

The controller checks de-energized digital output channels for potential short circuits.
Periodically, the controller partially turns on each de-energized output in turn and
measures the loop current. If the loop current shows a loop resistance of less than
approximately 10Ω, the controller reports a short circuit.

Advertising