After restoring the application, you must open the Communications Setup editor in
FactoryTalk View Studio, and re-apply the device path for each configured shortcut.
For details, see “To renew RSLinx Enterprise device paths” on page 73.

Backing up and restoring RSLinx Classic configurations

RSLinx Classic configuration files are not included when you back up a local station
application. You have to back up, move, and restore the files manually.

If RSLinx Classic is installed on the development and production computers, you can use
the RSLinx Classic Backup/Restore tool to back up and restore configuration files.

To move RSLinx Classic configuration files

1. On the development computer, click Start > All Programs > Rockwell Software >

RSLinx, and then click RSLinx Classic Backup Restore Utility.

2. In the RSLinx Classic Backup/Restore tool, click Backup.

3. Select a folder for the backup file, type a file name, and then click Save.

4. In Windows Explorer, copy the backup file, and then paste it into a location on the

data server production computer.

5. On the production computer, click Start > All Programs > Rockwell Software >

RSLinx, and then click RSLinx Classic Backup Restore Utility.

6. In the RSLinx Classic Backup/Restore tool, click Restore.

7. Find and select the backup file you just moved, and then click Open.

You can also restore RSLinx Classic configuration files from the Wizard Completed window of
the RSLinx Classic software setup program.