Rockwell Automation FactoryTalk View Site Edition Installation Guide User Manual

Page 135

Advertising
background image

9

U

PGRADING

AN

OPERATING

F

ACTORY

T

ALK

V

IEW

SE

APPLICATION

121

• •

Step 8 – Test the migrated FactoryTalk View SE application

To test the migrated application before upgrading remaining application computers,
perform these tasks:

Start Server #2 and wait for it to finish starting

Run the migrated application on upgraded clients

Verify that the system is functioning as expected

Start Server #2 and wait for it to finish starting

If Server #2 is not already started, start the server and wait for the server to finish starting.

To confirm that Server #2 has finished starting

1. Click Start > All Programs > Rockwell Software > FactoryTalk Tools, and then

click Diagnostics Viewer.

2. In the FactoryTalk Diagnostics Viewer, check for the following Diagnostics message:

The HMI Server <ApplicationName>//Server #2 is the active server.

Run the migrated application on upgraded clients

On each of the upgraded run-time client computers, run the existing FactoryTalk View
SE Client configuration file (.cli).

Verify that the system is functioning as expected

After the application starts running on the upgraded client computers, verify that display
navigation, object animation, communications, alarming (if configured), and other
applications features are functioning as expected.

To find a message faster in the Diagnostics Viewer, on the View menu, click Options. Then,
in the Filter tab, create a Message filter with one or more keywords from the message.

FTViewSEInstallENU.book Page 121 Wednesday, July 16, 2014 10:53 AM