Rockwell Automation FactoryTalk View Site Edition Installation Guide User Manual
Page 123

9
•
U
PGRADING
AN
OPERATING
F
ACTORY
T
ALK
V
IEW
SE
APPLICATION
109
•
•
•
• •
To back up a network distributed application
1. On Server #1, click Start > All Programs > Rockwell Software, and then click
FactoryTalk Administration Console.
2. In the Select FactoryTalk Directory dialog box, select Network, and then click OK.
3. In the Explorer window, right-click the application you want to back up, and then
click Backup.
4. Specify an archive name and location.
To specify a location other than the default, type the path or click the Browse button to
find and select a location.
5. Select the check box, Backup System in archive and then click OK.
The back-up operation saves an application archive file with a .bak extension to the
specified location. The default locations are:
C:\Users\Public\Documents
(Windows XP, and Windows Server 2003) C:\Documents and Settings\All
Users\Documents
Before backing up an application, record the user names and passwords of administrative users
set up for the application, in case this information is required for the restore operation.
FTViewSEInstallENU.book Page 109 Wednesday, July 16, 2014 10:53 AM