Start Server #1 and Server #2
To prepare to restart the entire system, first restart Server #1, and then start Server #2.
Wait for both servers to finish starting, and also confirm that they are functioning in their
primary and secondary roles.
To confirm that Servers #1 and #2 have finished starting
1. Click Start > All Programs > Rockwell Software > FactoryTalk Tools, and then
click Diagnostics Viewer.
2. In the FactoryTalk Diagnostics Viewer, check for the following Diagnostics messages:
The HMI Server <ApplicationName>//Server #1 is the active server.
In service. the server RNA://$Global/<ApplicationName>:
<HMIServerName> on computer Server #2 (secondary) is now on standby.
Start all run-time clients
To ensure that the entire, upgraded application is functioning as expected, run the existing
FactoryTalk View SE Client configuration file on each run-time client computer.
To find a message faster in the Diagnostics Viewer, on the View menu, click Options. Then,
in the Filter tab, create a Message filter with one or more keywords from the message.