For information about setting up other data server properties, click Help in the server’s
Properties dialog box, or see the product documentation.

To change the RSLinx Enterprise server computer name

1. Click Start > All Programs > Rockwell Software, and then click FactoryTalk

Administration Console (you can also perform this procedure in Studio Enterprise).

2. In the Select FactoryTalk Directory dialog box, select Network, and then click OK.

3. In the Explorer window, expand the name of the restored application, right-click the

RSLinx Enterprise server’s name, and then click Properties.

4. In the General tab, in the field, Computer hosting the RSLinx Enterprise server,

type the name of the production computer, or click Browse to find and select the
computer, and then click OK.

To change the RSLinx Classic server computer name

1. Open the restored application in the FactoryTalk Administration Console. To learn

how to do this, see the previous task.

2. In the Explorer window, expand the name of the restored application, right-click the

RSLinx Classic server’s name, and then click Properties.

3. In the General tab, in the field, Computer that will run the OPC server, type the

name of the production computer, or click Browse to find and select the computer, and
then click OK.

Renew data server shortcuts, topics, and device paths

After restoring RSLinx data servers in the application, and specifying the names of their
new host computers, renew or verify the topics, shortcuts, and device paths associated
with each data server, as needed.

If you are restoring redundant data servers, then the device paths must be confirmed and
reapplied for both the primary and the secondary server.

To renew RSLinx Enterprise device paths

1. Open the restored application in the FactoryTalk Administration Console. To learn

how to do this, see “To change the RSLinx Enterprise server computer name” above.

2. In the Explorer window, expand the data server (RSLinx Enterprise), and then double-

click Communications Setup.

The first time you open an application after relocating a data server, if the server does not load,
you should still be able to open the Properties dialog box and change the host computer name.
After the computer name is updated, the server should load as expected.