2 using the lcd oim to configure the module, 3 setting the node address – Rockwell Automation RECOMM-485 RS485 DFI Communications Module User Manual
Page 24

4-2
RS485 DF1 Communications Module
4.2
Using the LCD OIM to Configure the
Module
Use the procedure in figure 4.1 to access the parameters on the
RS485 DF1 module using the LCD OIM. If you are unfamiliar with
the operation of the LCD OIM, refer to the SP600 AC Drive User
Manual (D2-3485 or D2-3501) for more information.
4.3
Setting the Node Address
If the Data Rate switch on the module is set to “PGM,” the value of
module parameter 3 (DF1 Addr Cfg) determines the node address.
Step 1.
Set the value of module parameter 3 (DF1 Addr Cfg) to a
unique node address.
Step 2.
Reset the module. Refer to section 4.7.2, Resetting the
Module.
Figure 4.1 – Accessing the Module Parameters using the LCD OIM
P0: SP600
>>
Auto
Stopped
Main Menu
Device Select
Use to select
RECOMM-485.
P0: SP600
>>
Auto
Stopped
P5: RECOMM-485
>>
Auto
Stopped
Main Menu
Parameters
Device: Port 0
SP600
RECOMM-485
Monitor
Lang
Edit the RS485 DF1
parameters using the
same techniques as for
drive parameters.
Use to highlight
Device Select icon
Figure 4.2 – RS485 DF1 Node Address Screen on an LCD OIM
Port 5 Device
RECOMM-485
Parameter #: 3
DF1 Addr Cfg
1
0 <> 99
Default = 1