B-4

RS485 DF1 Communications Module

This parameter is a command. It resets the module if set to “Reset
Module.” It restores the module to factory default settings if set to
“Set Defaults.” No action is taken if set to “Ready.” The parameter
resets to “0 = Ready” after the command is performed.

Sets the action that the module takes when the module detects that
RS485 DF1 communications have been disrupted. This setting is
effective only if I/O that controls the drive is transmitted though the
module.

9

Reset Module

Range:

0 = Ready (No action)
1 = Reset Module
2 = Set Defaults (Restores module to factory-default

settings)

Default:

0 = Ready

Type:

Read/Write

Reset Required: No

!

ATTENTION: If the module is transmitting I/O that
controls the drive, the drive may fault when you reset
the module. Determine how your drive will respond
before resetting a connected module. Failure to
observe this precaution could result in bodily injury
or damage to equipment.

10

Comm Flt Action

Range:

0 = Fault
1 = Stop
2 = Zero Data
3 = Hold Last
4 = Send Flt Cfg

Default:

0 = Fault

Type:

Read/Write

Reset Required: No

!

ATTENTION: Comm Flt Action (module parameter
10) lets you determine the action of the module and
connected drive if communications are disrupted. By
default, this parameter faults the drive. You can set
this parameter so that the drive continues to run.
Take precautions to ensure that the setting of this
parameter does not create a hazard of injury or
equipment damage. Failure to observe this
precaution could result in bodily injury or damage to
equipment.