RS485 DF1 Module Parameters

B-5

Displays the source from which the module node address and data
rate are taken. This will either be switches on the module or
parameters in EEPROM. The source is determined by the settings
of the switches on the module. See chapter 3, Installing the RS485
DF1 Module, for more information about the switches.

Configures the I/O that is transferred through the module. See
figure B.1

11

Active Cfg

Range:

0 = Switches
1 = EEPROM

Default:

0 = Switches

Type:

Read Only

Reset Required: N/A

12

DPI I/O Cfg

Range:

See figure B.1.

Default:

xxx0 0001

Type:

Read/Write

Reset Required: Yes

Figure B.1 – DPI I/O Config (Parameter 12)

0

0

0

1

0

x

x

x

0

1

2

3

4

5

6

7

1 = I/O Enabled
0 = I/O Disabled
x =Not Used

Cmd/Ref

Datalink A

Datalink B

Datalink C

Datalink D

Not Used

Not Used

Not Used