Troubleshooting the Module and Network
6-7
6.3
Viewing and Clearing Events
The module maintains an event queue that reports the history of its
actions. You can view the event queue using an LCD OIM or
VS Utilities software.
To View and Clear Events Using an LCD OIM
Use the procedure shown in figure 6.2 to access the event queue
using the LCD OIM. Note that you must have the RECOMM-485
module as the selected device to access the event queue.
34
PCCC I/O Timeout The I/O communication timeout value (secs)
before the action selected in module parameter
10 (Comm Flt Action) is taken.
35
Data Rate SW
The value of the Data Rate switch on the module.
36
Node Address SW
The value of the Node Address switch on the
module.
Table 6.5 – Module Diagnostic Items (Continued)
No.
Event
Description
Figure 6.2 – Viewing and Clearing Events Using an LCD OIM
Diagnostics:
Device Version
OIM Version
View Event Queue
P0: RECOMM-485
Stopped Auto
Main Menu
Diagnostics
EvtQ# : E#xxxxx
Online @ 500kbps
1
Clrqu
Highlight Diagnostics icon
Highlight item
Monitor
Lang
>>
Press F2 key to
clear event queue